The Floodline® Multi-Zone Control Panel is available as 4-zone, 8-zone and 16-zone panel options designed for surface mounting. The control panel continuously monitors a network of multiple leak detection zones. With updated technology and enhanced installer and end-user functionality, the Floodline® Multi-Zone Control Panel is a truly multi-functional and customisable water, oil and gas leak detection control panel.
A zone can be anything from a single point to multiple liquid, gas and oil sensors as well as distance measuring liquid leak detection cable for up to 1500 metres via Floodline Ranger®. The whole network is continuously monitored for leaks and continuity. The system can also monitor humidity and temperature in any zone as required.
Zones are isolated from each other and individually displayed so the system can accept and report any number of simultaneous or consecutive zone alarms delivering true multiple leak reporting. If an alarm is triggered in any zone, it has no affect on the monitoring of any other zone and the rest of the system.
Temperature and humidity sensors can be configured for four separate alarm levels.
A leak detection alarm is indicated by a flashing LED as well as an audible alarm with mute function. All alarms are displayed separately and continuously until corrected and reset.
Output relays provide the ability to drive other devices such as beacons, remote alarms and solenoid valves to shut off water, gas and oil supply in the event of a leak.
The Floodline® One-Zone Control Panel is designed for surface mounting. The control panel continuously monitors a single leak detection zone.
A zone can be anything from a single point to multiple water, gas and oil sensors as well as distance measuring liquid leak detection cable for up to 1500 metres via Floodline Ranger®. The system can also monitor humidity and temperature as required.
A leak detection alarm is indicated by a flashing LED as well as an audible alarm with mute function. An activated alarm is displayed continuously until corrected and reset.
Output relays provide the ability to drive other devices such as beacons, remote alarms and solenoid valves to shut off water, gas and oil supply in the event of a leak.
Floodline Ranger® is a distance measuring system comprising control panel and detection cable providing leak detection for up to 1500 metres. Ranger® can operate as a stand-alone system or can easily be integrated into a larger Floodline® installation, functioning as a zone, connecting to any Floodline® control panel. The system is ideal for data centres, plant rooms, warehouses, libraries, museums and any longer areas that require water leak detection. The system provides more choice for those customers who require a distance measuring system with the advantage of also working within a network of multiple zones and a range of other sensors in any size of installation.
In the event of a leak detection, the control panel triggers an audio visual alarm as well as triggering onward communication to BMS or similar. Illuminated LEDs on the control panel provide visual indication for power, leak detection, system status alerts and communications. The leak detection LED indicator on the control panel shows the distance to the leak.
The high-visibity sensor cable detects the presence of water (or oil if oil sensor cable is used) at any point along its length. Detection cable is available in a range of pre-terminated lengths with locking connectors to join the lengths together. Conductive-polymer technology and fluoro-polymer construction make the water sensor cable mechanically strong and highly resistant to corrosion and abrasion. Oil sensor cable uses radiation-crosslinking and conductive-polymer technology to make the cable strong and chemically resistant.
Ranger® water sensor cable dries and resets within 15 minutes after removal from standing water and can be wiped with a clean, damp cloth. Ranger® oil sensor cable cannot be reset after a leak and the affected section needs to be replaced.
Floodline® 1-Zone Module is a self-contained single zone leak detection module specially designed for incorporation into other control/alarm systems, air conditioning units, BMS etc. The module continuously monitors a single leak detection zone.
Floodline® 1-Zone Module provides two volt-free contacts for communication with flashing LEDs signalling independently RED for leak detection and YELLOW for system status alarms. All alarms are displayed continuously until corrected and reset.
The module provides variable sensitivity for leak alarm, the ability to read sensor status, manual and automatic reset modes, a history log of the last five alarm events, two volt-free relay outputs and test operation for the volt-free contacts.
The compact module is designed for DIN rail mounting and screw terminals provide connections for leak detection sensors, power input and volt-free contact output.
Floodline® 8-Way SVCP monitors alarm relays in a Floodline® control panel and automatically controls the operation of solenoid or motorised valves to isolate a water, oil or gas source when a leak is detected. Floodline® 8-Way SVCP is available in eight configurations to control up to eight 24Vdc 16 Watt solenoid valves.
The SVCP has illuminated power and alarm indicators, fuse protection for each power output, output for both normally open and normally closed valves and a valve test button for testing the operation of the valves.